Brass for internal or external use for SWA cable, with outer seal giving moisture proof protection, to BS6121 (where applicable.

Can be supplied with Shroud, Locknut and Earth tag if required.

Not B.A.S.E.E.F.A. approved.

CW Dimensions

S denotes small cable entry size

Brass and aluminium are not compatible metals and contact between them can result in electrolysis action, therefore precautions must be taken when connecting Brass Glands to Aluminium enclosures or to the Aluminium armouring of cables.

CW with outer seal for SWA cable

ISO Metric Thread entry size MM Dimensions Diameter over thread MM Equivalent imperial thread size inches Minimum entry thread length 'D' mm Assembled length excl. thread entry 'E' MM Hexagon Size
Bore 'A' Cable 'B' Across corners 'F' MM
MM Min MM Max MM
20/16 8.7 8.0 13.5 0.9 3/4 10.0 41.0 24.5
20S 11.7 11.2 16.0 0.9 / 1.25 3/4 10.0 44.0 30.5
20 14.0 13.2 21.0 0.9 / 1.25 3/4 10.0 46.0 33.5
25S 20.0 15.5 24.0 1.25 / 1.6 1 10.0 51.0 40.0
25 20.0 22.5 27.5 1.25 / 1.6 1 10.0 51.0 40.0
32 26.3 26.4 34.0 1.6 / 2.0 1 1/4 10.0 51.5 51.5
40 32.2 31.5 40.5 1.6 / 2.0 1 1/4 15.0 55.0 61.5
50S 38.2 36.4 46.8 2.0 / 2.5 2 15.0 54.5 67.0
50 44.1 42.9 52.8 2.0 / 2.5 2 15.0 55.0 79.0
63S 56.0 46.8 60.5 2.5 2 1/2 15.0 68.5 89.0
75S 62.0 60.0 71.8 2.5 3 15.0 76.5 102.0
75 68.0 64.5 78.1 2.5 3 15.0 74.5 111.5
90 79.4 65.0 90.5 2.5 3.15 15.0 88.5 129.0

 