BS5308 Cable
CSE Cables supplies the full range of BS5308 cables included Part 1 - Type 1 - Unarmoured : Collectively Screened and Individually & collectively screened
Part 1 - Type 2 - Armoured : Collectively Screened and Individually & collectively screened
BS5308 Part 1 / Type 1 Unarmoured Construction
1. Plain annealed copper wire conductors to BS 6360
2. Type 03 polyethene insulation to BS 6234
3 Individual pair screen (optional):-
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification
4 Polyester binder tape
5 Collective screen (optional) - Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
6 Type TM1 or Type 6 PVC sheath to BS 7655
BS5308 Part 1 / Type 2 Armoured Construction
1 Plain annealed copper wire conductors to BS 6360
2 Type 03 polyethene insulation to BS 6234
3 Individual pair screen (optional):-
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification
4 Polyester binder tape
5 Collective screen (optional) - Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
6 Type 03C black polyethylene bedding to BS 6234
7 Single layer galvanised steel wire armour to BS EN 10257-1
8 Type TM1 PVC sheath to BS 7655
BS5308 Part 2 / Type 1 (unarmoured)
1 Plain annealed copper wire conductors to BS 6360
2 Type TI1 PVC to BS 7655
3 Individual pair screen (optional):-
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification
4 Polyester binder tape
5 Collective screen (optional) - Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
6 Type TM1 or Type 6 PVC sheath to BS 7655
BS5308 Part 2 / Type 2 (armoured)
1 Plain annealed copper wire conductors to BS 6360
2 Type TI1 PVC to BS 7655
3 Individual pair screen (optional):-
a) Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
b) Polyester isolating tape(s) numbered for identification
4 Polyester binder tape
5 Collective screen (optional) - Aluminium/polyester tape, metallic side down, in contact with minimum 0.5mm2 tinned copper drain wire
6 Type TM1 PVC bedding to BS 7655
7 Single layer galvanised steel wire armour to BS EN 10257-1
8 Type TM1 PVC sheath to BS 7655 |