CSE Cable
CSE Cables - Supplier of industrial cable
BS5308 Cable
BS5308 Part 1
Type 1 Unarmoured
- Collectively Screened
- Individually & collectively screened
Type 2 Armoured
- Collectively Screened
- Individually and Collectively Screened
- Part 1 Technical Data
- Part 1 Unscreened Pairs
BS5308 Part 2
Type 1 Unarmoured
- Multipair Collectively Screened
- Multipair Collectively screened
- Multipair, individually and collectively screened
Type 2 Armoured
- Multipair collectively screened
- Multipair collectively screened
- Multipair individually and collectively screened
- Part 2 Technical Data
- Part 2 Unscreened Pairs
BS5308 LSF
BS5308-1-1 0.75 1P LSF
BS5308-1-1 0.75 1Q LSF-2

BS5308 LSF CableBS5308-1-1 0.75 1P LSF

PART NUMBER: Varies with colour and packing.

DESCRIPTION:
Circular 1-pair, 0.75mm² Flex Plain Copper, XLPE Insulated, Collective Al/Pol Screened,
HFLSF Sheathed, BS 5308: Part 1, Type 1, a.f.a.a.

CONDUCTORS:
0.75mm² plain annealed copper bunch meeting the requirements of BS EN 60228, class 5.

INSULATION:
Type GP 8 XLPE meeting the requirements of BS 7655.
Nominal radial thickness = 0.6mm.

LAY UP:
One Black and one Blue core.

SCREEN:
Aluminium/Polyester laminated tape, incorporating a 0.5mm² (16/0.2mm) tinned copper drain wire.

SHEATH:
Halogen free, low smoke and fume compound to BS 7655.
Nominal overall diameter = 6.45mm.
Printed: CSE CABLES BS 5308-1 TYPE 1 1P 0.75 #### XLPE HFLSF
(where #### = year).

SERVICE DATA:
Not suitable for connection to low impedance source, e.g. mains voltage.
Maximum working voltage: 300/500V ac rms.
Test voltage: 1000V ac rms. between conductors and between conductors and screen.
Maximum conductor operating temperature: +90°C.
Minimum ambient temperature: -15°C after installation and only when cable is in fixed position.
Maximum conductor d. c. resistance at 20°C: 26.0Ω/km.
Minimum insulation resistance: 5GΩ.km at 20°C
Maximum L/R ratio: 25μH/Ω.
Maximum mutual capacitance at 1kHz: 115pF/m.
Sheath oxygen index: >30.
Resistance to vertical flame propagation: passes BS EN 60332.
Smoke density of burning cable: passes BS EN 61034.
Gas emission during combustion: level of HCl, <0.5% by weight of compound.
Approximate mass/unit length: 52kg/km.

CSE Cables : Unit 16, Wessex Road, Bourne End, Bucks, SL8 5DT
Tel : 01628 850024; Fax : 01628 648068; Email :