FP+ CableThe Prysmian / Pirelli FP Plus for Enhanced application areas.
Click to buy
Prysmian FP Plus on-line now.
Fire detection and fire alarm systems for buildings. FP PLUS is BASEC and LPCB approved in accordance with the requirements of BS5839-1:2002 Clause 26.2 for Enhanced fire resisting cables
Conductor : Plain annealed copper solid conductor complying with BS6360 class 1
Insulation : Cross-linked damage resistant insulation (Type E15)
Core identification
brown-blue
brown-black-grey
blue-brown-black-grey
Screen : Laminated Copper tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor.
Sheath :
Robust thermoplastic LSOH sheath
Colour - Red
Other colours to special order.
| Bending Radius | Fixed r = 8D |
| Fire Performance | BSEN50265-2-1 BSEN50266-2-4 |
| Fire Resistant | BS6387 category CWZ EN50200 PH120 BS8434-2 |
| Flexibility | Rigid |
| Halogen Free | BSEN50267-2-1 |
| Mechanical Impact | Medium |
| Low Smoke Emissions | BSEN50268-2 |
| Temperature Range | -20 to +70oC |
| Nominal cross sectional area mm2 |
Conceptual Construction no. / mm |
Mean overall diameter mm |
Approximate cable weight kg/km |
Maximum conductor resistance at 20oC ohms / km |
Current rating DC or single phase AC Enclosed Amps |
Current rating DC or single phase AC clipped direct Amps |
Volt drop DC or single phase AC mV / A / m |
| Two Core | |||||||
| 1.0 | 1/1.13 | 8.5 | 110 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1/1.38 | 9.4 | 125 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1/1.78 | 11.0 | 170 | 7.4 | 23 | 27 | 18 |
| Three Core | |||||||
| 1.0 | 1/1.13 | 9.0 | 125 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1/1.38 | 10.0 | 150 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1/1.78 | 11.0 | 210 | 7.4 | 23 | 27 | 18 |
| Four Core | |||||||
| 1.0 | 1 / 1.13 | 10.3 | 160 | 18.1 | 13 | 15 | 44 |
| 1.5 | 1/1.38 | 11.0 | 190 | 12.1 | 16.5 | 19.5 | 29 |
| 2.5 | 1/1.78 | 12.6 | 270 | 7.4 | 23 | 27 | 18 |