FP100 Cable
Prysmian FP100® is the original fire resistant single core cable for use in metal conduits or trunking to achieve a highly robust fire resistant wiring system. It maintains circuit integrity during a fire both when tested in free air or in a metallic conduit. When burnt, it produces very low levels of smoke and virtually no (less than 0.5%) acidic gases, thus safeguarding human life and protecting equipment.
Through the use of a dual layer insulation system, FP100® offers fire resistance combined with abrasion and damage resistance, making it an excellent choice both for upgrading existing conduit based systems to current essential safety circuit standards or new installations.
Systems based upon standard pvc cables, even when protected by metal conduit, have been shown to fail within minutes in a fire. Therefore they are no longer permitted by BS5839-1 or BS5266-1for fire alarm or emergency lighting systems, as they do not ensure prolonged operation in the event of a fire.
This cable has a maximum core temperature of 90oC and is used in fire alarm systems, emergency lighting and in power safety circuits when installed in conduits or protected trunking.
| Type Approval Certificates : |
LPCB - Loss Prevention Certification Board |
| |
FSD : Fire Services Department |
Conductor : Stranded bare copper class 2 IEC 60228
Primary Insulation : Mineral ceramic (Mica / Glass) fire resistant tape
Secondary Insulation : 90oC high performance cross linked mineral filled insulation
Marking
- 1 x S mm2 - 0.6 / 1kV
- MX 331
- IEC 60331, BS 6387 cat. CWZ
- LPCB 253d / 01
Core Identification : Colours : red, black, blue, yellow, white, green / yellow
Fire resistant : IEC 60331, BS 6387 CWZ; SS 299 CWZ
Fire retardant : IEC 60332 Part 3 & 1; EN 50265 1 & 2.1
Low Smoke : IEC 61034; NFC 32-073; EN 50268; BS 7622
Halogen Free : IEC 60754; NFC 32-074; EN 50267; BS 6425
Low corrosivity - IEC 60754; NFC 32-074; EN 50267; BS 6425
Temperature : -20 + 60oC
Nominal Cross Sectional Area
mm2 |
Approximate Overall Diameter
mm |
Approximate cable weight
Kg / Km |
Maximum conductor resistance at 20oC
ohms / km |
Short Circuit rating (1 sec)
Amps |
Current rating DC or single phase AC
Amps |
Current rating Three phase AC
Amps |
Volt drop DC
mV / A/ m |
Volt drop Single phase AC
mV / A/ m |
Volt drop Three phase AC
mV/A/m |
| 1.5* |
3.5 |
26 |
12.1 |
215 |
22 |
19 |
31 |
31 |
27 |
| 2.5* |
4.1 |
38 |
7.41 |
360 |
30 |
26 |
19 |
19 |
16 |
| 4* |
4.6 |
54 |
4.61 |
570 |
40 |
35 |
12 |
12 |
10 |
| 6* |
5.2 |
75 |
3.08 |
860 |
51 |
45 |
7.9 |
7.9 |
6.8 |
| 10* |
6.6 |
120 |
1.83 |
1425 |
71 |
63 |
4.7 |
4.7 |
4 |
| 16 |
7.7 |
180 |
1.15 |
2275 |
95 |
85 |
2.9 |
2.9 |
2.5 |
| 25 |
9.0 |
270 |
0.727 |
3375 |
126 |
111 |
1.85 |
1.9 |
1.65 |
| 35 |
10.0 |
360 |
0.524 |
5000 |
156 |
138 |
1.35 |
1.35 |
1.15 |
| 50 |
11.7 |
490 |
0.387 |
7150 |
189 |
168 |
0.99 |
1.05 |
0.9 |
| 70 |
13.2 |
680 |
0.268 |
10000 |
240 |
214 |
0.68 |
0.75 |
0.65 |
| 95 |
15.3 |
940 |
0.193 |
13575 |
290 |
259 |
0.49 |
0.58 |
0.5 |
| 120 |
16.8 |
1160 |
0.153 |
17150 |
336 |
299 |
0.39 |
0.48 |
0.42 |
| 150 |
18.7 |
1440 |
0.124 |
21450 |
375 |
328 |
0.32 |
0.43 |
0.37 |
| 185 |
20.8 |
1800 |
0.0991 |
26450 |
426 |
370 |
0.25 |
0.37 |
0.32 |
| 240 |
23.5 |
2350 |
0.0754 |
34325 |
500 |
433 |
0.19 |
0.33 |
0.29 |
| 300 |
27.3 |
3000 |
0.0601 |
42925 |
573 |
493 |
0.155 |
0.31 |
0.27 |
| 400 |
32.5 |
3970 |
0.0470 |
57225 |
683 |
584 |
0.120 |
0.29 |
0.25 |
| 500 |
36.0 |
4980 |
0.0366 |
71525 |
783 |
666 |
0.093 |
0.28 |
0.24 |
| 630 |
40.0 |
6340 |
0.0283 |
90125 |
900 |
764 |
0.072 |
0.27 |
0.23 |
|