NX200 Cable
BS 5839-1 : 2002 Cat. Standard. 300 / 500 V. A fire resistant, fire retardant and low smoke cable for use in buildings where systems need to remain operational.
| Types Approval
Application :
- Fire detection and fire alarm systems for buildings
- Public address systems
- Emergency lighting
Design :
- Conductor : Bare copper, Solid Class 1 (1, 1.5mm2), Stranded Class 2 (2.5 4mm2) according to BS 6360 / IEC 60228
- Insulation : Silicon rubber to BS 7655
- Un-insulated protective conductor : Tinned copper according to BS6360 : same class and cross sectional area as insulated conductor.
- Screen : Aluminium / polyester tape with optional polyester tape
- Outer sheath : Halogen free polyolefin. colour : red or white
|
|
 |
Marking :
ALSECURE NX 200 - n x s
300 / 500 V - BASEC - LPCB - BS 7629-1 - BS 6387 CWZ - BS 8434-1 - NEXANS - week / year
Core identification :
2 cores : brown - blue
3 cores : brown - black - grey
4 cores : brown - black - grey - blue
Standards :
BS 7629 Part 1
BS 5839-1 : 2002 Cat. Standard
Electrical characteristics
Rated Voltage Uo/U 300 / 500 V
Usage characteristics
Fire resistant BS 6387 CWZ, BS 8434-1 : 2003; BS EN 50200 PH 30
Flame retardant BS EN 50265 1 & 2.1; IEC 60332 Part 1
Low smoke BS EN 50268; IEC 60754
Halogen free : BS EN 50267, IEC 60754
Low toxicity : BS EN 50267; IEC 60754
Low corrosivity : BS EN 50267; IEC 60754
Temperature : -20 + 60 oC
| Cables (mm2) |
Outer diameter (approx) |
Current rating (A) |
Voltage drop (V/A x km) |
Weight approx
(kg / km) |
| Min. (mm) |
Max. (mm) |
AC/DC 2 cores loaded |
AC 3 cores loaded |
| 2 x 1 |
6.8 |
8.2 |
15.0 |
44.0 |
|
87 |
| 2 x 1.5 |
7.3 |
8.7 |
19.5 |
29.0 |
|
103 |
| 2 x 2.5 |
9.2 |
10.8 |
27.0 |
18.0 |
|
164 |
| 2 x 4 |
10.5 |
12.3 |
36.0 |
11.0 |
|
247 |
| 3 x 1 |
7.3 |
9.6 |
13.5 |
|
38.0 |
102 |
| 3 x 1.5 |
7.8 |
10.0 |
17.5 |
|
25.0 |
123 |
| 3 x 2.5 |
9.8 |
12.7 |
24.0 |
|
15.0 |
198 |
| 3 x 4 |
11.2 |
14.1 |
32.0 |
|
9.5 |
295 |
| 4 x 1 |
8.2 |
10.6 |
13.5 |
|
38.0 |
125 |
| 4 x 1.5 |
8.7 |
11.2 |
17.5 |
|
25.0 |
151 |
| 4 x 2.5 |
10.9 |
14.1 |
24.0 |
|
15.0 |
242 |
| 4 x 4 |
12.4 |
15.3 |
32.0 |
|
9.5 |
362 |
These current and voltage drops data are indicated for continuous duty operation
They are as defined in BS 7671 : 2001
table 4D2A and apply to
- maximum conductor temperature = 70oC
- nominal frequencies = 50 - 60 Hz
On cable in air, clipped direct at ambient temperature = 30oC
Voltage drop
The data is based on Cos j = 1
For other laying conditions, refer to BS 7671 : 2001 standard |