Loading

Prysmian Mining CablesPrysmian Mining Cable BCS 295 3kV

Cable Construction

Constructional Data

Conductor cross-sectional area mm² 95 120 150 185 240 300
Conductor diameter sector shaped
Nominal Insulation thickness mm 2.0 2.0 2.0 2.0 2.0 2.0
Nominal Bedding sheath thickness mm 1.8 2.2 2.2 2.2 2.6 2.6
Armour - nominal diameter of wires mm 2.0 2.5 2.5 2.5 2.5 2.5
Nominal Oversheath thickness mm 2.3 2.4 2.5 2.6 2.7 2.8
Nominal Overall diameter of cable mm 44.0 48.0 51.0 54.0 60.0 64.0
               

Installation Data

             
Approximate Cable mass kg 4.90 6.20 7.30 8.50 10.60 12.60
Minimum bending radius mm 360 380 415 440 480 520
Maximum pulling tension (per conductor) kgf 475 600 700 700 700 700
               

Electrical Data

             
Maximum DC resistance of conductor @ 20°C Ω/km 0.193 0.153 0.124 0.0991 0.0754 0.0601
Maximum AC resistance of conductor @ 90°C Ω/km 0.247 0.196 0.159 0.128 0.097 0.080
Maximum resistance of armour wire @ 20°C Ω/km 0.322 0.255 0.207 0.165 0.126 0.100
Capacitance (core to core) μF/km 0.330 0.353 0.388 0.423 0.466 0.511
Approximate Inductance mH/km 0.254 0.249 0.242 0.238 0.233 0.228
Reactance @ 50Hz Ω/km 0.080 0.078 0.076 0.075 0.073 0.072
Impedance @ 50Hz Ω/km 0.260 0.211 0.175 0.147 0.123 0.107
Approximate Volt Drop (Three Phase) mV/A/m 0.45 0.37 0.30 0.26 0.21 0.190
               

Current Ratings (Three Phase)

             
Laid direct in ground Amps 304 345 387 436 502 563
Drawn into a duct Amps 257 293 328 371 428 480
Laid in air Amps 328 380 430 495 584 666
               
Short circuit rating conductor (1 second, adiabatic)              
(90 to 250°C) kA 13.6 17.2 21.4 26.5 34.3 42.9
               
Current rating conditions              
Air temperature °C            
Ground temperature °C            
Depth of burial (to centre of cable group) mm            
Thermal resistance of soil °C m/W            
Solid bonded and earthed at both ends.              

Note

Conductor sizes above 35mm² are shaped, and therefore Equvialent Circular Diameters have been stated for these sizes

© Copyright 2008 Prysmian Cables and Systems Ltd. All rights reserved.